Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 mode_status READ & WRITE 1280 1 fc3/fc16 bool reading: 0=stand-by/remote-off, 1=chiller mode/heat pump mode, writing only power off
1 on/off_status READ 1280 1 fc4 bool 1: on mode, 0: remote off
2 chiller_status READ & WRITE 1280 1 fc3/fc16 bool reading: 0=chiller off, 1= chiller on, writing: 1=chiller on
3 heat_pump_status READ & WRITE 1280 1 fc3/fc16 bool reading: 0= heat pump off, 1= heat pump on, writing: 1= heat pump on
4 buzzer_status READ & WRITE 1280 1 fc3/fc16 bool 1= stop buzzer
5 dinamic_set_point READ 1280 1 fc4 bool 1= set point active
6 energy_saving_mode READ & WRITE 1280 1 fc3/fc16 bool 1= energy saving mode active