| DEVICE DB | Impressum & Datenschutz |
| INDEX | NAME | DIRECTION | REGISTER | COUNT | FUNCTION | TYP | CONVERTION | ENUMS | UNIT |
|---|---|---|---|---|---|---|---|---|---|
| 0 | setpoint | READ & WRITE | 1 | 1 | fc3/fc16 | ui16 | |||
| 1 | fanspeed | READ & WRITE | 2 | 1 | fc3/fc16 | ui16 | 1|2|3 | low|high|high2 | |
| 2 | mode | READ & WRITE | 3 | 1 | fc3/fc16 | ui16 | 0/1/2/3/4 | auto/heating/ventilator/cooling/drying | |
| 3 | slat | READ & WRITE | 4 | 1 | fc3/fc16 | ui16 | 1/2/3/4/5/6/7 | sway/0°/20°/45°/70°/90°/- | |
| 4 | on/off | READ & WRITE | 5 | 1 | fc3/fc16 | ui16 | 0/1 | off/on | |
| 5 | rc_operation_mode | READ | 51 | 1 | fc4 | ui16 | 0/1/2/3 | idle,ventilator/heating/cooling/heating and cooling | |
| 6 | unit_count | READ | 20 | 7 | fc4 | ui16 | |||
| 7 | is_fault | READ | d6 | ui16 | 0/1 | no fault/at least one device has one disturbance | |||
| 8 | fault_code | READ | d6 | ui16 | |||||
| 9 | return_air | READ | d6 | ui16 | x/100 | °C | |||
| 10 | filter_alarm | READ | d6 | ui16 | 0/1 | no alarm/at least one device has one filter alarm | |||
| 11 | return_air_min | READ | d6 | ui16 | x/100 | °C | |||
| 12 | return_air_max | READ | d6 | ui16 | x/100 | °C | |||
| 13 | thermostat_on | READ | 1 | fc4 | ui16 | 0/1/2/3 | idle,ventilator/heating/cooling/heating and cooling | ||
| 14 | defrost | READ | 1 | fc4 | ui16 | 0/1 | no defrosting/at leas one device in in defrost mode |