INDEX ALIAS NAME UNIT
0 DEVICE Device
1 DEVICE_VER_(B/P) Device ver. (B/P)
2 TEMP_FRESH_AIR_CUR Current fresh air temp C/10
3 TEMP_APT_CUR Current apartment temp C/10
4 PRESSURE_SUPPLY_CHNL Supply chnl pressure Pa
5 PRESSURE_EXHAUST_CHNL Exhaust chnl pressure Pa
6 FLOW_SETPOINT_[M3/H] Setpoint flow m^3/h
7 PRESSURE_IMB_OK Pressure imbalance ok 0=Balanced, 1=Imbalance airflow
8 PRESSURE_FIXED_IMB Fixed press imbalance m^3/h
9 FLOW_SUPPLY_CUR Current supply flow m^3/h
10 FLOW_EXHAUST_CUR Current exhaust flow m^3/h
11 BYPASS_FLAP_POS Bypass flap pos 0=Init, 1=Opening, 2=Closing, 3=Open, 4=Closed, 255=Unknown
12 BYPASS_FLAP_FUNC Bypass flap func 0=Auto, 1=Bypass closed, 2=Bypass open
13 PREHEAT_REG_STATUS Preheat reg status 0=Init, 1=Inactive, 2=Active, 3=Test mode, 255=Unknown
14 POWER_PREHEAT_REG Preheat reg power %
15 ERROR_CODE_CUR Current error code 0=No error
16 FILTER_DISPLAY Filter display 0=Clean, 1=Dirty
17 GROUND_HEAT_MODE Ground heat mode 0=Off, 1=On
18 TEMP_GROUND_MIN Min ground heat temp C/10
19 TEMP_GROUND_MAX Max ground heat temp C/10
20 CO2_SENSOR_NUM CO2 sensor # (max4)
21 CO2_SENSOR_VALUE CO2 sensor value ppm
31 FLOW_SETPOINT Setpoint flow m^3/h
32 PRESSURE_IMB_OK Pressure imbalance ok
33 PRESSURE_FIXED_IMB Fixed press imbalance m^3/h
34 BYPASS_MODE_FUNC Bypass mode func
35 FILTER_RESET_CMD Filter reset (cmd) 1=Reset
36 GROUND_HEAT_MODE Ground heat mode
37 TEMP_GROUND_MIN Min ground heat temp C/10
38 TEMP_GROUND_MAX Max ground heat temp C/10
40 BRINK_RESET_CMD Reset Brink (cmd) 1=Reset device
41 CTRL_MODE_SET_CMD Set control mode (cmd) 0=Brink device, 1=Modbus
200 QUALITY Quality