| INDEX | NAME | DIRECTION | REGISTER | COUNT | FUNCTION | TYP | CONVERTION | ENUMS | UNIT |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Current_flow_temperature_HC2 | READ | 1514 | 1 | fc3 | si16 | x/10 | °C | |
| 2 | Current_hot_water_cylinder_temperature_setpoint | READ | 1499 | 1 | fc3 | si16 | x/10 | °C | |
| 3 | Mode_HC1 | WRITE | 1478 | 1 | fc6 | ui16 | 0=Standby 1=Woche 1 2=Woche 2 4=Konstant 5=Sparbetrieb 7=Manuell Heizen 8=Manuell Kühlen | ||
| 4 | Mode_HC2 | WRITE | 1479 | 1 | fc6 | ui16 | 0=Standby 1=Woche 1 2=Woche 2 4=Konstant 5=Sparbetrieb 7=Manuell Heizen 8=Manuell Kühlen | ||
| 5 | Current_flow_temperature_HC1 | READ | 1513 | 1 | fc3 | si16 | x/10 | °C | |
| 6 | Status_producer_temperature_setpoint | READ | 18724 | 1 | fc3 | si16 | x/10 | °C | |
| 7 | Current_producer_flow_temperature_HC1 | READ | 18725 | 1 | fc3 | si16 | x/10 | °C | |
| 8 | Current_outside_temperature | READ | 1477 | 1 | fc3 | si16 | x/10 | °C | |
| 9 | Current electrical power | READ | 25611 | 1 | fc3 | si16 | x/10 | kW | |
| 10 | Current thermal power | READ | 25612 | 1 | fc3 | si16 | x/10 | kW | |
| 11 | Status_flow_temperature_setpoint_HC1 | READ | 19562 | 1 | fc3 | si16 | x/10 | °C | |
| 12 | Status_flow_temperature_setpoint_HC2 | READ | 19563 | 1 | fc3 | si16 | x/10 | °C | |
| 13 | Set_flow_temperature_heating_HC1 | WRITE | 1490 | 1 | fc6 | si16 | x*10 | °C | |
| 14 | Set_flow_temperature_heating_HC2 | WRITE | 1491 | 1 | fc6 | si16 | x*10 | °C | |
| 15 | Hot_water_temperature_setpoint | WRITE | 1497 | 1 | fc6 | si16 | x*10 | °C | |
| 16 | Set_flow_temperature_cooling_HC1 | WRITE | 19482 | 1 | fc6 | si16 | x*10 | °C | |
| 17 | Set_flow_temperature_cooling_HC2 | WRITE | 23755 | 1 | fc6 | si16 | x*10 | °C |