Zehnder ComfoConnect Pro

Unità di ventilazione • MODBUS TCP (DDF)

Zehnder
Scarica DDF firmato Versione min. OS: V9615-09
Device image

The ComfoConnect Pro DDF allows you to connect your Zehnder ventilation system to your automation system and remotely control airflow, monitor sensor values, adjust settings, and check the system status.

Create a VENTILATION block and, under IO Configuration, set an individual type. Then assign "Set Level Analog" under Outputs/Contacts for the analog output.

Status messages are available in the System DEVICE.

Produttore Tipo Protocollo Modello Versione ID
Zehnder Unità di ventilazione MODBUS TCP (DDF) 1 1 0x0A00008000010100
ID Nome Unita Tipo Direzione
0 Error Flag 1 = Fault bool IN
1 Connection State 0 = Ok, 30 = Wrong Device, 40 = Incompatible, 50 = No Device word IN
2 Ventilation Preset 0 = Off, 1 = S1, 2 = S2, 3 = S3 word IN
3 Airflow m^3/h word IN
4 Room Temperature C/10 int IN
5 Extract Temperature C/10 int IN
6 Exhaust Temperature C/10 int IN
7 Outdoor Temperature C/10 int IN
8 Supply Temperature C/10 int IN
9 Room Humidity % word IN
10 Extract Humidity % word IN
11 Exhaust Humidity % word IN
12 Outdoor Humidity % word IN
13 Supply Humidity % word IN
14 Filter Remaining Days word IN
15 Filter Dirty 1 = Filter Dirty bool IN
100 Set Level Analog 0-25p = Off, 25-50p = S1, 50-75p = S2, 75-100p = S3 int OUT
101 Set Temperature Profile 0 = Normal, 1 = Cool, 2 = Warm word OUT
102 Set Temperature Mode 0 = Adaptive, 1 = Fixed, 2 = Setpoint word OUT
103 Set Temperature Setpoint C/10 word OUT
104 Set Auto Mode 1 = Auto bool OUT
105 Set Error Reset 1 = Reset bool OUT
200 Quality 1 = Ok bool IN
201 Timestamp s dword IN