TopTronic E
Description
The Hoval TopTronic E (TTE) is an operating system for Hoval district heating, Air/Water, Brine/Water and Water/Water heat pumps, as well as gas, oil and wood heat sources, which can be used standalone or combined into hybrid systems for heating and cooling.
It can also operate a Hoval ventilation system.
In addition, the TopTronic E (TTE) can communicate with the Hoval PV-Heater.
This DDF defines the device’s inputs and outputs, provides visualization and error checking within the DEVICE system, and sets the ventilation mode to Constant.
Attention: This DDF supports only following HOVAL Use Cases for Heating&Cooling, PV-Heater & HomeVent ER at the moment:
-
Use case 1: Setpoint specification for room temperature and domestic hot water via Modbus
-
Use case 2: Setpoint specification for flow temperature and domestic hot water via Modbus
-
Use case 3: Specification of a temperature setpoint via Modbus directly to the heat generator
-
Use case 4: Specification of a power setpoint via Modbus directly to the heat generator
-
Use case 5: Control of the HomeVent ventilation system via Modbus
-
Use case 6: Power limitation for Germany in accordance with Section 14a of the German Energy Industry Act (EnWG) / grid-supportive control via Modbus
-
Use case 7: Reading information values from the heat generator or the ventilation system via Modbus – details
Further Details can be found on the dedicated Hoval Webpage:
General Info
| Manufacturer | Type | Protocol | Model | Version | ID |
|---|---|---|---|---|---|
| Hoval | Gateway | MODBUS TCP (DDF) | 1 | 1 | 0x0A00004100010100 |
Documents
DDF Items
| ID | Name | Unit | Type | Direction |
|---|---|---|---|---|
| 0 | Airflow Set FB | % | ||
| 1 | Exhaust Humidity | % / 327.67 | ||
| 2 | Exhaust VOC | % | ||
| 3 | Outdoor VOC | % | ||
| 4 | Ventilation Status | 0=Off, 1=Normal, 2=VOC, 3=Humidity, 4=Frost, 5=CoolVent, 6=Error, 7=SummerHum, 8=StopOff | ||
| 5 | Supply Temp | C/10 | ||
| 6 | Exhaust Temp | C/10 | ||
| 7 | Airflow Actual | % | ||
| 8 | Vent Mode | 0=Standby, 1=W1(Hoval), 2=W2(Hoval), 4=Constant, 5=ECO | ||
| 100 | Set Vent Mode | 0=Standby, 1=W1(Hoval), 2=W2(Hoval), 4=Constant, 5=ECO | ||
| 120 | Set Fan Level 1 | |||
| 121 | Set Fan Level 2 | |||
| 122 | Set Fan Level 3 | |||
| 123 | Set Fan Level 4 | |||
| 180 | Connection | |||
| 200 | Quality |